KODY BŁĘDÓW POMP CIEPŁA SOLA

Wpisz kod błędu, a następnie naciśnij przycisk wyszukiwania.

Nr błęduTreść błęduMiejsceBłądPotwierdzenie (ręcznie)Aktyw.1. wiadomość o staniePraca pompy ciepłaOdpowiedzialność (nr)Postępowanie
----------
10Outside sensorB96NieNie---Tak1 (Instalator)
25Boiler sensor solid fuelB226NieNie---Tak1 (Instalator)
26Common flow sensorB106NieNie---Tak1 (Instalator)
27Common flow sensor 2B116NieNie---Tak1 (Instalator)
28Flue gas temp sensorB86NieNie---Tak1 (Instalator)
30Flow sensor 1B16NieNie---Tak1 (Instalator)
31Flow sensor cooling 1B166NieNie---Tak1 (Instalator)
32Flow sensor 2B126NieNie---Tak1 (Instalator)
33Flow sensor HPB216NieNie---Tak1 (Instalator)
35Source inlet sensorB919NieNie---Nie (param)1 (Instalator)
36Hot-gas sensor 1B816NieNie---Tak1 (Instalator)
37Hot-gas sensor 2B826NieNie---Tak1 (Instalator)
38Flow sensor prim contrB156NieNie---Tak1 (Instalator)
39Evaporator sensorB849NieNie---Nie (air-HP)1 (Instalator)
43Return sensor solid fuelB726NieNie---Tak1 (Instalator)
44Return sensor HPB716NieNie---Tak1 (Instalator)
45Source outlet sensorB929NieNie---Nie (param)1 (Instalator)
46Return sensor cascadeB706NieNie---Tak1 (Instalator)
47Common return sensorB736NieNie---Tak1 (Instalator)
48Refrigerant sensor liquidB836NieNie---Tak1 (Instalator)
50DHW sensor 1B36NieNie---Tak1 (Instalator)
52DHW sensor 2B316NieNie---Tak1 (Instalator)
54DHW flow sensorB356NieNie---Tak1 (Instalator)
57DHW circulation sensorB396NieNie---Tak1 (Instalator)
60Room sensor 16NieNie---Tak1 (Instalator)
65Room sensor 26NieNie---Tak1 (Instalator)
68Room sensor 36NieNie---Tak1 (Instalator)
70Storage tank sensor 1B46NieNie---Tak1 (Instalator)
71Storage tank sensor 2B416NieNie---Tak1 (Instalator)
72Storage tank sensor 3B426NieNie---Tak1 (Instalator)
73Collector sensor 1B66NieNie---Tak1 (Instalator)
74Collector sensor 2B616NieNie---Tak1 (Instalator)
76Special sensor 1Bx3NieNie---Tak1 (Instalator)
81LFB short-circuit/comm6NieNie---Tak5 (Brak)
82LFB address collision3NieNie---Tak5 (Brak)
83BSB short-circuit8NieNie---Tak5 (Brak)
84BSB address collision3NieNie---Tak5 (Brak)
85BSB Radio communication8NieNie---Tak5 (Brak)
98Extension module 18NieNie---Tak5 (Brak)
99Extension module 28NieNie---Tak5 (Brak)
1002 clock time masters3NieNie---Tak5 (Brak)
102Clock without backup3NieNie---Tak5 (Brak)
105Maintenance message5NieNie---Tak1 (Instalator)
106Source temp too low6TakNie---Nie1 (Instalator)
107Hot-gas compressor 19TakNum*Limit hot-gas compr 1Nie2 (Obsługa klienta)
117Water pressure too highHx6NieNie---Tak1 (Instalator)
118Water pressure to lowHx6NieNie---Nie1 (Instalator)
121Flow temp HC1 (zu tief)3NieNie---Tak1 (Instalator)
122Flow temp HC2 (zu tief)3NieNie---Tak1 (Instalator)
126DHW charg temp6NieNie---Tak1 (Instalator)
127Legionella temp6NieNie---Tak1 (Instalator)
134Common fault HPE209TakNum*FaultNie1 (Instalator)
138No control sensor HP1NieNie---Nie1 (Instalator)
146Configuration error3NieNie---Tak5 (Brak)
171Alarm contact 1 activeH1/H316NieNie---Tak1 (Instalator)
172Alarm contact 2 activeH2/H21/H22/H326NieNie---Tak1 (Instalator)
173Alarm contact 3 activeEx6NieNie---Tak1 (Instalator)
174Alarm contact 4 activeH3/H336NieNie---Tak1 (Instalator)
176Water press 2 too highHx6NieNie---Tak1 (Instalator)
177Water press 2 too lowHx6NieNie---Nie1 (Instalator)
178Limit thermostat HC13NieNie---Tak1 (Instalator)
179Limit thermostat HC23NieNie---Tak1 (Instalator)
201Frost alarmB219TakNie---Nie1 (Instalator)
204Fan overloadE149TakNum*Fan overloadNie1 (Instalator)
222Hi-press on HP opE109TakNum*High-press HP in operationNie1 (Instalator)
223Hi-press on start HCE109TakNie---Nie1 (Instalator)
224Hi press on start DHWE109TakNie---Nie1 (Instalator)
225Low-pressureE99TakNum*Low-pressureNie2 (Obsługa klienta)
226Compressor 1 overloadE119TakNum*Compressor 1 overloadNie2 (Obsługa klienta)
228Flow swi heat sourceE159TakNum*Flow switch heat sourceNie1 (Instalator)
229Press swi heat sourceE159TakNum*Press switch heat sourceNie1 (Instalator)
230Source pump overloadE149TakNum*Source pump overloadNie1 (Instalator)
241Flow sensor yieldB636NieNie---Tak1 (Instalator)
242Return sensor yieldB646NieNie---Tak1 (Instalator)
243Swimming pool sensorB136NieNie---Tak1 (Instalator)
247Defrost fault9TakNum*Prehating for defrostNie1 (Instalator)
260Flow sensor 3B146NieNie---Tak---
320DHW charging sensorB366NieNie--Tak---
321DHW outlet sensorB386NieNie---Tak---
322Water press 3 too highHx6NieNie---Tak---
323Water press 3 too lowHx6NieNie---Nie---
324BX same sensors3NieNie---Tak---
325BX/e'module same sens3NieNie---Tak---
326BX/m'grp same sens3NieNie---Tak---
327E'module same funct3NieNie---Tak---
328Mix group same funct3NieNie---Tak---
329E'mod/m'grp same funct3NieNie---Tak---
330Bx1 no function3NieNie---Tak---
331Bx2 no function3NieNie---Tak---
332Bx3 no function3NieNie---Tak---
333Bx4 no function3NieNie---Tak---
334Bx5 no function3NieNie---Tak---
335Bx21 no function3NieNie---Tak---
336Bx22 no function3NieNie---Tak---
337B1 no function3NieNie---Tak---
338B12 no function3NieNie---Tak---
339Coll pump Q5 missing3NieNie---Tak---
340Coll pump Q16 missing3NieNie---Tak---
341Coll sensor B6 missing3NieNie---Tak---
342Solar DHW B31 missing3NieNie---Tak---
343Solar integration missing3NieNie---Tak---
344Solar buffer K8 missing3NieNie---Tak---
345Sol swi pool K18 missing3NieNie---Tak---
346Boiler pump Q10 missing3NieNie---Tak---
347Solid fuel boil comp sens3NieNie---Tak---
348Solid fuel boil addr err3NieNie---Tak---
349Buff valve Y15 missing3NieNie---Tak---
350Buffer address error3NieNie---Tak---
351Prim/sys pump addr err3NieNie---Tak---
352Pr'less header addr err3NieNie---Tak---
353Casc sens B10 missing3NieNie---Tak---
354Special sensor 2Bx3NieNie---Tak---
3553-ph curr asymmetricE21/E22/E239TakNum*3-ph current asymmetricNie---
356Flow switch consumersE249TakNum*Flow switch consumersNie---
357Flow temp cooling 1 (not achieved)6NieNie---Tak---
358Soft starterE259YesNum*---Nie---
359Div valve cool Y21 miss3NieNie---Yes---
360roc rev va Y22 miss3NieNie---Tak---
361Source sens B91 miss3NieNie---Tak---
362Source sens B92 miss3NieNie---Tak---
363Compr sens B84 miss3NieNie---Tak---
364Cool system HP wrong3NieNie---Nie---
365Inst heater Q34 miss3NieNie---Tak---
366Room temp sensor Hx6NieNie---Tak---
367Room humidity sens Hx6NieNie---Tak---
368Flow temp setp readjHx6NieNie---Tak---
370Thermodynamic source9NieNie---Nie---
369External9NieNie---Nie---
371Flow temp HC3 (too low)3NieNie---Tak---
372Limit thermostat HC33NieNie---Tak---
373Extension module 33NieNie---Tak---
385Mains undervoltage E21E219TakNum*Mains
388DHW sensor no function3NieNie---Tak---
441BX31 no function3NieNie---Tak---
442BX32 no function3NieNie---Tak---
443BX33 no function3NieNie---Tak---
444BX34 no function3NieNie---Tak---
445BX35 no function3NieNie---Tak---
446BX36 no function3NieNie---Tak---
447BX6 no function3NieNie---Tak---
452HX1 no function3NieNie---Tak---
453HX3 no function3NieNie---Tak---
454HX31 no function3NieNie---Tak---
455HX32 no function3NieNie---Tak---
456HX33 no function3NieNie---Tak---
457BX7 no function3NieNie---Tak---
462BX8 no function3NieNie---Tak---
463BX9 no function3NieNie---Tak---
464B107 no function3NieNie---Tak---
465BX11 no function3NieNie---Tak---
466BX12 no function3NieNie---Tak---
467BX13 no function3NieNie---Tak---
468BX14 no function3NieNie---Tak---
469HX21 no function3NieNie---Tak---
470HX22 no function3NieNie---Tak---
472Flow sensor cooling 2B176NieNie---Tak---
473Flow sensor cooling 3B186NieNie---Tak---
474Flow temp cooling 2 (nicht erreicht)6NieNie---Tak---
475Flow temp cooling 3 (nicht erreicht)6NieNie---Tak---
476Suction gas sensorB856NieNie---Nie---
477Evapor press sensor H82H826NieNie---Nie---
479No refrigerant selected3NieNie---Nie---
480Suction gas sensor EVIB866NieNie---Nie---
481Evap press sensor EVIH866NieNie---Nie---
482Evapor temp sensor EVIB876NieNie---Nie---
484Div valve cool Y45 miss3NieNie---Tak---
488Condens press sensorH838NieNie---Nie---
489No cascade master3NieNie---Tak---
490Cascade source miss3NieNie---Tak---
491Max evaporation temp9TakNum*Limitation evap temp maxNie---
492K2/modulat incompatible3NieNie---Nie---
493Outside air sensorB196NieNie---Tak---
494Outside air Q17 missingQ173NieNie---Tak---
495Modbus no comm'cation6NieNie---Tak---
496Flow sw source int circ9TakNum*Flow switch source int circNie---
497Pres sw sourc int circ9TakNum*Press switch source int circNie---
498Air quality sensor HxHx6NieNie---Tak---
499External source missing3NieNie---Nie---
500Modbus configuration3NieNie---Tak---
501Suction gas sensor 2B886NieNie---Nie---
502Sourc int circ flow sensB936NieNie---Nie---
503Sourc int circ ret sensB946NieNie---Nie---
504Press diff proc reversal6TakTakLimit press diff proc reversNie1 (Instalator)
505Expansion valve evap6TakNie---Nie---
506Suppl source missing6NieNie---Tak---
511Leg temp circ pipe6NieNie---Tak---
517Room humidity sensor 16NieNie---Tak---
518Room humidity sensor 26NieNie---Tak---
519Room humidity sensor 36NieNie---Tak---
521Modbus slave port 16NieNie---Tak/Nie**---
522Modbus slave port 26NieNie---Tak/Nie**---
523Modbus slave port 36NieNie---Tak/Nie**---
524Modbus slave port 46NieNie---Tak/Nie**---
525Modbus slave port 56NieNie---Tak/Nie**---
526Modbus slave port 66NieNie---Tak/Nie**---
527Modbus slave port 76NieNie---Tak/Nie**---
528Modbus slave port 86NieNie---Tak/Nie**---
529Superheat controller6NieNie---Nie---
530Superheat controller 26NieNie---Nie---
531Special sensor 36NieNie---Tak---
532Special sensor 46NieNie---Tak---
533Special sensor 56NieNie---Tak---
534Special sensor 66NieNie---Tak---
535Special sensor 76NieNie---Tak---
536Special sensor 86NieNie---Tak---